Current position:Home » Products » Battery Test Equipment » Ground Fault Locator
Ground Fault Locator
Cost can be tremendous upon bad insulation or grounding in the power system. It may even cause power break-off which is costly to repair. Fast localization and elimination of insulation faults will be significant for electricians and technicians. It is also required by DIN VDE 0100-410 (VDE 0100-410): 2007-06 chapter 411.6.3.1 and IEC 60364-4-41 chapter 413.1.5.4. PITE 3830 is developed to fast detect, track and locate virtual grounding faults on DC systems. This spares you from hours of unnecessary troubleshooting and helps to increase the reliability of your electrical equipment. It is widely used in locomotive, telecom, power utilities, etc.
  • Design features
  • Product function
  • Technical parameter

There is loose of electricity to the ground in the breakage of busbar and thus generate a faulty "grounding". When testing leads of PITE 3830 are connected to the ground and busbar, there will be a return circuit. Signal generator (main unit) will send a low-frequency voltage signal of 0.1Hz~1000Hz between the testing target and grounding malfunctioned circuit. The breaking point will generate leaking current. As the grounding receiver (signal receiver) moves in the circuit, different points in the circuit will have different reaction in the indication of sound warning. It will pinpoint the cable fault basing on the sound volume in the signal receiver.

Ground Fault Locator

This is the flowchart for ground-fault location in DC system.
It indicates the cable connection and simple way to pinpoint faulty "Grounding".

Two function in one: Insulation tester and ground fault locator
Test and record insulation status of facilities
No disconnection of the electrical installation, ground fault location is carried out during operation.
Fast locations for ground fault even when cables are buried unearth.
Signal-generator with adjustable frequency and voltage, convenient for testing.
Reflects aging status of facilities for further reparation.
Powerful management software on PC for trouble analyzing .
Reduced maintenance and repair costs.
Measuring range
V testing: 0.00-1000V
Insulation resistance: 20kΩ-500MΩ (250V)
50kΩ-1000MΩ (500V)  100 kΩ-2000MΩ (1000V)
Min resolution
Voltage: 0.1V   Insulation R: 0.01 MΩ
Accuracy
Voltage: 1%rdg±8dgt
Insulation R: 0.5 MΩ-100 MΩ 5%rdg±6dgt
﹥100 MΩ: 10%rdg±6dgt
Output signal
voltage: 0-1000V±10%   Frequency: 1-1000Hz
Power consumption
≥4 hours(continuous operation)
Memory
32k×8bit Non Volatile SRAM
Displaying screen
128×64 pixels LCD
Communication
USB interface
Battery
Li-ion
Dimension
490*370*250mm
Weight
7KG
Humidity
80%R.H
Temperature
-5℃-40℃
Receiver
Testing accuracy
≤0.25MΩ
Power voltage
DC 8.4V
Sensor aperture
59mm
Jaw opening
66mm