Power Quality Meter
An easy-to-use power quality tool is a ”must-have” for any person who maintains or troubleshoots three phase power. PITE 3531 three-phase power quality analyzer helps you locate, predict, prevent and troubleshoot problems in power distribution systems. We offer a full range of trouble-shooters for the prevention and analyzing of the power quality problems. It is not only your problem solver, but also money saver.
  • Design features
  • Product function
  • Technical parameter
  • Portable design and colorful touch screen
  • Applied to standard of EN 50160
  • Could test 3-phase 3-wire and 3-phase 4-wire
  • Up to 50 times harmonic testing with frequency spectrum graph
  • 3-phase apparent power, active power, reactive power, power factor, and 3-phase electric energy.
  • 3-phase unbalance testing with vivid chart
  • Record at least 40 times of surge current
  • Testing for wave motion, short-time flicker and long-time flicker
  • Record up to 40 times of sag and swell
  • Could have long-time record for basic (stable) power quality parameter. Recording time interval adjustable between 3 second and 30 minutes.
  • Digital oscilloscope, checking waveform for voltage and current signal
  • With PITE DataView software for convenient analyzing of testing result
  • Trouble-elimination: fast measurement and display on screen for trouble-shooting
  • Predictive maintenance: test to avoid power quality problem before malfunction happens
  • Service function: measurement for power quality before users lead-in
  • Long time analysis: recording function help find out unobvious and occasional malfunction
  • Load analysis: check quality of electric system before adding loads
  • Energy evaluation: evaluate energy consumption before installation of energy-saving facilities
  • Specifications
    Range
    Accuracy
    Volt/Amp/Hertz
    Volt: 10~700V (true rms)
    Amps: 0.5~3000A (true rms, with relevant current clamp)
    Current Peak: 0-3000A
    Volt Peak: 0-1000V
    Crest factor: 0-10
    Hertz: 40~70Hz
    Volts: ±0.5%
    Amps: ±0.5%
    Hertz: ±0.01Hz
    NOTE: Take frequency of Phase A as total testing frequency.
    Harmonic
    Volts: total harmonic +1~50th
    Amps: total harmonic +1~50th
    k-factor: 0-10
    Volts: ±0.1(%r)
    Amps: ±1%
    ±0.5%
    Power testing
    Active Power: 0.05~700KW
    Apparent Power: 0.05~700KVA
    Reactive Power: 0.05~700KVAR
    Power Factor: 0.00~1.00
    Active Energy: 0.01~10000kWh
    Apparent Energy: 0.01~10000kVAh
    Reactive Energy: 0.01~10000kVARh
    Average Power Factor: 0.00~1.00
    Active Power: ±1%
    Apparent Power: ±1%
    Reactive Power:±1%
    Power Factor: ±0.005
    Active Energy: ±1%
    Apparent Energy: ±1%
    Reactive Energy: ±1%h
    Average Power Factor: ±0.005
    Unbalance
    Fundamental Volts: 10~700V (true rms)
    Fundamental Amps: 0.5~1000A (True rms)
    Fundamental Hertz: 40~70Hz
    Phase Angle: 0~360°
    Unbalance: 0.0%~100%
    Volts: ±0.5%
    Amps: ±0.5%
    Hertz: ±0.01Hz
    Phase Angle: ±0.3°
    Volt unbalance:  ±0.2%
    NOTE: Take frequency of Phase A as total testing frequency.
    Data Recording
    Recording for: 3 phase voltage, current, null current, voltage harmonic (THD and 1~25 harmonics), current harmonics ( THD and 1~25 harmonics), unbalance, KW, KVA,KVAR, PF, flicker and fluctuation


    Time interval: 3s~30min adjustable
    Time duration: <960 hours
    Sags(Dips)/Swells
    Volts sag, Volts Swells and instant interruption
    Maximally could record 40 times
    Fluctuation
    Voltage Fluctuation:0.1%~10.0%
    ≤±5%
    Flicker
    Short-time and long-time flicker
    Short-time: ≤±5%
    Scope
    3-phase Volts, 4-wire Current, null volt and null current waveform
    Max Hertz: 200KHz
    Min Hertz: 100Hz